-40%

A12-701 Ranco Commercial Temperature Cold Control for Coolers Auto Defrost!!!

$ 47.49

Availability: 100 in stock
  • Model: A12-701
  • All returns accepted: ReturnsNotAccepted
  • Condition: New
  • Color: Silver
  • Type: Thermostat
  • MPN: A12-701
  • Brand: Ranco

    Description

    Gregoriou Brothers Refrigeration Since 1979
    Frosty-Freeze
    Cooler Temp Control Thermostat, RANCO A12-701, Coil Sensing Auto Defrosting. NEW
    RANCO A12-701
    A12-651 A12-1741 A12-802 Coil Sensing Refrigerator Thermostat
    COOLER THERMOSTAT
    This is the only
    thermostat
    I use on cooler jobs that I have a coil ice-up problem.
    It is awesome for all cooler applications as well.
    The important thing to know about this thermostat is the sensor or the end of the sensor must be inserted into the evaporator coil, (between the fins) at least 4" in so it can sense the coil temperature not the air temperature.
    It is a control that works by sensing the coil temperature not the air temperature.
    By doing this it prevents the coil from icing up and allows the temperature to drop as the coil can handle the load.
    I always place the probe into the last row of coils leaving the evaporator giving me the whole coil to use.
    When this control feels the coil icing up, it turns the compressor off until the coil temperature is 41 degrees thus insuring there is nor ice on the coil.
    The range on this control is  15 F to 31 F
    The automatic or constant on setting is 41 F.
    The capillary tubing is 84" long.
    RANCO A12-701 A12-651 A12-1741 A12-802 Coil Sensing Refrigerator Thermostat COOLER THERMOSTAT This is the only thermostat I use on cooler jobs that I have a coil ice-up problem. It is awesome for all cooler applications as well. The important thing to know about this thermostat is the sensor or the end of the sensor must be inserted into the evaporator coil, (between the fins) at least 4" in so it can sense the coil temperature not the air temperature. It is a control that works by sensing the coil temperature not the air temperature. By doing this it prevents the coil from icing up and allows the temperature to drop as the coil can handle the load. I always place the probe into the last row of coils leaving the evaporator giving me the whole coil to use. When this control feels the coil icing up, it turns the compressor off until the coil temperature is 41 degrees thus insuring there is nor ice on the coil. The range on this control is 15 F to 31 F The automatic or constant on setting is 41 F. The capillary tubing is 84" long.
    Gregoriou Brothers Refrigeration Since 1979
    Frosty-Freeze
    Cooler Temp Control Thermostat, RANCO A12-701, Coil Sensing Auto Defrosting. NEW
    RANCO A12-701
    A12-651 A12-1741 A12-802 Coil Sensing Refrigerator Thermostat
    COOLER THERMOSTAT
    This is the only
    thermostat
    I use on cooler jobs that I have a coil ice-up problem.
    It is awesome for all cooler applications as well.
    The important thing to know about this thermostat is the sensor or the end of the sensor must be inserted into the evaporator coil, (between the fins) at least 4" in so it can sense the coil temperature not the air temperature.
    It is a control that works by sensing the coil temperature not the air temperature.
    By doing this it prevents the coil from icing up and allows the temperature to drop as the coil can handle the load.
    I always place the probe into the last row of coils leaving the evaporator giving me the whole coil to use.
    When this control feels the coil icing up, it turns the compressor off until the coil temperature is 41 degrees thus insuring there is nor ice on the coil.
    The range on this control is  15 F to 31 F
    The automatic or constant on setting is 41 F.
    The capillary tubing is 84" long.
    RANCO A12-701
    A12-651 A12-1741 A12-802 Coil Sensing Refrigerator Thermostat
    COOLER THERMOSTAT
    This is the only
    thermostat
    I use on cooler jobs that I have a coil ice-up problem.
    It is awesome for all cooler applications as well.
    The important thing to know about this thermostat is the sensor or the end of the sensor must be inserted into the evaporator coil, (between the fins) at least 4" in so it can sense the coil temperature not the air temperature.
    It is a control that works by sensing the coil temperature not the air temperature.
    By doing this it prevents the coil from icing up and allows the temperature to drop as the coil can handle the load.
    I always place the probe into the last row of coils leaving the evaporator giving me the whole coil to use.
    When this control feels the coil icing up, it turns the compressor off until the coil temperature is 41 degrees thus insuring there is nor ice on the coil.
    The range on this control is  15 F to 31 F
    The automatic or constant on setting is 41 F.
    The capillary tubing is 84" long.